STATUS SETTINGS & CONTROL

Module #3 - Setup

Output Voltage Control
Temperature Coefficient / cell: mV/°C

Battery Charge Current Limit
Charge Current Limit: A(10 - 150)

Equalize Charge
Equalize Voltage: VDC(46.0 - 62.0)
Equalize Duration: minutes(10 - 240)
Equalize Interval: days(0 - 180)
Day of Week:
Start Time: : (HH : MM)

Caution: For use with flooded batteries only (see Instruction Manual).

Periodic Equalize Charge will be disabled if the Equalize Interval is set to 0 days or if NTP synchronization is not configured.

The Battery must be fully charged and the DC Output enabled before a Equalize Charge can be started.

Manual Equalize Charge is Not Ready.

Last Equalize Charge:09/13/21 16:12:45
Charge Time:60 min

Next Equalize Charge:

Disabled

Configure Battery
Battery Capacity: Ah(50 - 1000)
Rate: Hour Rate

LVD Settings
Disconnect Voltage: VDC(42.0 - 48.0)
Reconnect Voltage: VDC(46.0 - 52.0)

Battery Over-Current Alarm
Over-Current Threshold:> A(0 - 150)

Over-Current Alarm will be disabled if the threshold is set to 0 Amps.

Battery Low SOC Alarm
SOC Threshold:< %

Alarm Reporting
When an alarm is triggered on this module,
Activate Alarm Form C Contact:
Send E-mail:

Battery Discharge Test
Set Discharge Time: minutes(10 - 240)
Set Discharge Voltage Limit: VDC(42.5 - 52.0)
Discharge Test Interval: days(0 - 180)
Day of Week:
Start Time: : (HH : MM)

Periodic Battery Discharge Tests will be disabled if the Discharge Test Interval is set to 0 days or if NTP synchronization is not configured.

Discharge Voltage Limit must be set higher than the LVD Disconnect Voltage.

The Battery must be fully charged and the DC Output enabled before a Battery Discharge Test can be started.

Manual Discharge Test is Not Ready.

Last Battery Discharge Test:07/02/21 11:53:07
Status:Complete
Discharge Time:60 min
End Voltage:48.10 VDC
Amp-Hours Discharged:19 Ah

Next Periodic Discharge Test:

Disabled